Pump Starter Kits – Contactor + Overload + Phase Relay

Pump & Motor Starter Kits – Schneider TeSys D

Everything a direct-on-line starter for a 3-phase pump or motor needs: a TeSys D contactor, the matching TeSys LRD thermal overload relay, and the Zelio RM35TF30 phase-control relay that trips the motor on phase loss, phase reversal or unbalance – the most common cause of burnt motors on unstable grids and generator supply.

Motor (400 V, 3-phase) Contactor (AC-3) Overload relay Phase protection
4 kW LC1D09 LRD14 (7–10 A) RM35TF30
18.5 kW LC1D40A LRD340 (30–40 A) RM35TF30
22 kW LC1D50A LRD350 (37–50 A) RM35TF30
30 kW LC1D65A LRD365 (48–65 A) RM35TF30
45 kW LC1D95 LRD3365 (80–104 A) RM35TF30

Coil 220 V AC (M7) as standard; 24 V / 48 V / 110 V coils on request. Pairings follow the Schneider TeSys D catalogue for standard 400 V motors. The final selection is confirmed by our engineer from your motor nameplate (kW, rated current, voltage).

Project and bulk orders: send the motor nameplate photo and quantity on WhatsApp for a quotation.


أطقم تشغيل الطلمبات والمواتير – شنايدر TeSys D

كل اللي محتاجه لتشغيل طلمبة أو موتور 3 فاز: كونتاكتور، والأوفرلود المناسب له، وريلاي حماية الفاز RM35TF30 اللي بيفصل الموتور عند سقوط فاز أو عكس الفازات أو عدم الاتزان – أكتر سبب لحرق المواتير مع الشبكة غير المستقرة والمولدات.

قدرة الموتور 4 / 18.5 / 22 / 30 / 45 كيلووات – راجع الجدول أعلاه للاختيار. ابعت صورة لوحة بيانات الموتور والكمية على واتساب وهنحدد لك الطقم المناسب ونبعت عرض السعر.