Skip to product information
1 of 1

Schneider Electric

Schneider Electric GV3P73 TeSys GV3 Motor Circuit Breaker 3P 62–73 A Thermal-Magnetic | MPCB

Schneider Electric GV3P73 TeSys GV3 Motor Circuit Breaker 3P 62–73 A Thermal-Magnetic | MPCB

Regular price LE 13,197.50 EGP
Regular price Sale price LE 13,197.50 EGP
Sale Sold out
Taxes included.
Quantity

The Schneider Electric GV3P73 is a TeSys GV3 thermal-magnetic motor circuit breaker with a setting range of 62–73 A. It protects three-phase motors against overload, short circuit and phase failure, and can also be used to start and stop the motor manually – replacing a breaker plus overload relay in one compact unit.

Key features

  • Adjustable thermal setting 62–73 A to match the motor nameplate current
  • Phase-failure sensitivity for three-phase motors
  • Clear ON/OFF/TRIP indication and lockable handle for safe maintenance
  • Direct mounting with TeSys contactors to build compact starters
  • Accepts auxiliary contacts, fault signalling contacts and undervoltage releases
  • DIN-rail or panel mounting

Technical specifications

Brand Schneider Electric
Part number (SKU) GV3P73
Product range TeSys GV3
Device type Motor circuit breaker / manual motor starter (MPCB)
Protection thermal-magnetic (overload + short circuit + phase loss)
Setting / rated current 62–73 A
Typical motor power (400 V AC-3) ≈ 37 kW
Poles 3P
Control Rotary handle
Mounting 35 mm DIN rail or panel
Standard IEC/EN 60947-2, IEC/EN 60947-4-1

Typical applications

  • Water pumps, booster sets and fire pumps
  • Fans, blowers, compressors and conveyors
  • HVAC, chiller and cooling-tower motors
  • Machine control panels and MCCs
  • Direct-on-line motor starters

Selection guide

Select the range so that the motor full-load current (from the nameplate) falls inside the setting range, then set the dial exactly to the nameplate current. For example, a 7.5 kW 400 V motor draws about 15 A, so a 13–18 A range is appropriate.

Frequently asked questions

What motor size suits the GV3P73?

With a 62–73 A setting range it suits three-phase motors whose full-load current lies within that range – roughly up to 37 kW at 400 V.

Do I need an overload relay with this breaker?

No for thermal-magnetic GV2ME/GV2P/GV3P/GZ1E types, which include overload protection. Yes for magnetic-only GV2L types, which must be combined with a thermal overload relay.

Buy Schneider GV3P73 in Egypt

Order the Schneider Electric GV3P73 from Spark Egypt and receive an original motor circuit breaker (MPCB) with an official tax invoice. We deliver to Cairo, Giza, New Cairo, 6th of October, Sheikh Zayed, the New Administrative Capital, Alexandria, the Delta, the Canal cities and Upper Egypt, and our engineers help contractors, panel builders and maintenance teams check ratings, accessories and cross-references before purchase. Request a project quotation for bulk quantities.