Skip to product information
1 of 1

Schneider Electric

Schneider Electric A9R44440 Acti9 iID RCCB 4P 40A 300mA Type AC | Earth Leakage Circuit Breaker

Schneider Electric A9R44440 Acti9 iID RCCB 4P 40A 300mA Type AC | Earth Leakage Circuit Breaker

Regular price LE 3,790.58 EGP
Regular price Sale price LE 3,790.58 EGP
Sale Sold out
Taxes included.
Quantity

The Schneider Electric A9R44440 is a 4-pole, 40A, 300 mA type AC residual current circuit breaker (RCCB) from the Acti9 iID range. It continuously compares the outgoing and returning current and disconnects the circuit when an earth-leakage current is detected, providing fire protection and protection of installations against earth-fault currents.

Key features

  • 300 mA sensitivity for fire protection and protection of installations against earth-fault currents
  • 4-pole version for three-phase + neutral installations
  • Test button to check correct operation periodically
  • Trip indication and positive contact indication
  • DIN-rail mounting, combines with MCBs in the same board
  • Must be used together with MCBs or upstream circuit breakers for short-circuit protection

Technical specifications

Brand Schneider Electric
Part number (SKU) A9R44440
Product range Acti9 iID
Device type Residual current circuit breaker (RCCB / ELCB)
Number of poles 4P
Rated current 40A
Sensitivity (IΔn) 300 mA
Residual current type Type AC
Rated voltage 230/400 V AC, 50/60 Hz
Mounting 35 mm DIN rail
Standards IEC/EN 61008-1

Typical applications

  • Apartment and villa main distribution boards
  • Bathrooms, kitchens, outdoor sockets and wet areas
  • Offices, schools, hospitals and commercial buildings
  • Water heater, pump and swimming-pool circuits
  • Compliance with Egyptian electrical code requirements for earth-leakage protection

Selection guide

Use 30 mA for protection of people, 300 mA for fire protection at the main incomer, and choose the rated current equal to or higher than the upstream MCB rating. A 2-pole RCCB is used for single-phase supplies; a 4-pole RCCB for three-phase supplies with neutral.

Frequently asked questions

Does the A9R44440 protect against short circuits?

No. An RCCB detects earth leakage only; it must be protected by an MCB or circuit breaker of equal or lower rating for overload and short-circuit protection.

Why does my RCCB trip frequently?

Nuisance tripping is usually caused by real insulation faults, moisture in outlets or appliances with high leakage such as old water heaters. Test each circuit separately to locate the fault.

What is the difference between an RCCB and an RCBO?

An RCCB provides earth-leakage protection only, while an RCBO combines earth-leakage and overcurrent (MCB) protection in one device.

Buy Schneider A9R44440 in Egypt

Spark Egypt is a trusted source for original Schneider Electric residual current circuit breaker (RCCB)s such as the A9R44440, serving contractors, OEMs, panel builders and plant-maintenance teams with tax invoices and fast delivery to Cairo, Giza, New Cairo, 6th of October, Sheikh Zayed, the New Administrative Capital, Alexandria, the Delta, the Canal cities and Upper Egypt. Contact our technical sales team to confirm selection, accessories and project pricing.

View full details