Hager
Hager MC MCB 2P 10–63 A C-Curve 6 kA | Miniature Circuit Breaker Range
Hager MC MCB 2P 10–63 A C-Curve 6 kA | Miniature Circuit Breaker Range
Couldn't load pickup availability
The Hager MC is a 2P 10–63 A C-curve miniature circuit breaker with 6 kA breaking capacity. It protects cables and connected equipment against overload and short circuit in single-phase circuits where phase and neutral are switched together, and clips onto a standard 35 mm DIN rail in apartment, villa, commercial and industrial distribution boards. This listing covers several current ratings – choose the rating that matches your cable size.
Key features
- C-curve characteristic suited to general loads such as lighting, sockets, air conditioners and small motors (magnetic trip at 5–10 × In)
- 2P construction for single-phase circuits where phase and neutral are switched together
- Breaking capacity 6 kA for safe disconnection of short-circuit currents
- Clear ON/OFF handle with contact position indication for safe isolation
- Quick clip-on mounting on 35 mm DIN rail, compatible with standard pin/fork busbars
- Compact modular width for neat, standardised distribution boards
Technical specifications
| Brand | Hager |
|---|---|
| Part number / model | MC |
| Device type | Miniature circuit breaker (MCB) |
| Number of poles | 2P |
| Rated current (In) | 10–63 A |
| Tripping curve | C curve |
| Breaking capacity | 6 kA |
| Rated voltage | 230/400 V AC, 50/60 Hz |
| Mounting | 35 mm DIN rail |
| Standard | IEC/EN 60898-1 |
Available versions
Current: 10A, 16A, 20A, 25A, 32A, 40A, 63A.
Typical applications
- Apartment, villa and office distribution boards
- Lighting, socket-outlet and air-conditioning circuits
- Commercial buildings, shops, schools and hospitals
- Control panels, pump panels and HVAC panels
- Replacement of old or faulty breakers during maintenance
Selection and installation tips
Match the breaker rating to the cable cross-section (typically 10 A for 1.5 mm² lighting, 16–20 A for 2.5 mm² sockets, 25–32 A for 4–6 mm² air-conditioner lines), choose the curve according to the inrush current of the load, and make sure the breaking capacity exceeds the prospective short-circuit current at the board. Add an RCCB or use an RCBO for earth-leakage protection.
Frequently asked questions
What is the Hager MC used for?
It is a 2P 10–63 A C-curve MCB used to protect single-phase circuits where phase and neutral are switched together against overload and short circuit.
Does an MCB protect against electric shock?
No. An MCB protects cables against overload and short circuit only. For protection of people against earth leakage use a 30 mA RCCB upstream or an RCBO.
Which MCB rating do I need for an air conditioner?
As a guide, 1.5–2.25 HP split units usually use a 16–20 A C-curve MCB, 3 HP units 25 A and 4–5 HP units 32 A, always matched to the cable size recommended by the manufacturer.
Buy Hager MC in Egypt
Order the Hager MC miniature circuit breaker (MCB) from Spark Egypt and receive a genuine product with an official tax invoice. We deliver to Cairo, Giza, New Cairo, 6th of October, Sheikh Zayed, the New Administrative Capital, Alexandria, the Delta, the Canal cities and Upper Egypt, and our engineers help contractors, installers and maintenance teams check ratings, accessories and cross-references before purchase. Request a quotation for bulk or project quantities.